Trane RTU Error Code 45 – Causes and Troubleshooting

Written by

in

What Does Trane RTU Error Code 45 Mean?

On many Trane rooftop units, Error Code 45 indicates a supply fan proving switch fault or airflow verification failure. The controller is not receiving confirmation that the supply fan is operating as expected.

When this fault occurs, the unit may:

  • Prevent compressor operation
  • Disable heating or cooling stages
  • Enter lockout mode

Common Causes of Error Code 45

Typical causes include:

  • Failed airflow proving switch
  • Broken or loose tubing to pressure switch
  • Dirty filters
  • Failed supply fan motor
  • Blower belt failure (belt-driven units)
  • Faulty fan contactor
  • Control board input issue

Airflow restrictions are among the most common causes.


How to Troubleshoot

1. Verify Fan Operation

Confirm the supply fan motor is running when commanded.

Check:

  • Motor amperage
  • Belt condition
  • Shaft rotation

2. Inspect Airflow Proving Switch

Check:

  • Tubing for cracks or blockage
  • Proper pressure differential
  • Electrical continuity

Replace the switch if it does not close under proper airflow.

3. Inspect Filters and Coil

Restricted airflow can prevent the proving switch from closing.

Replace dirty filters and clean coils as needed.


When to Replace Components

Replace the airflow switch if:

  • It fails continuity under proper airflow
  • Tubing is intact but no signal is present

Only suspect control board failure after verifying mechanical components.


FAQ

Will the unit cool with this fault active?
Usually no. The unit prevents operation without verified airflow.

Is this a serious fault?
It protects the equipment from operating without airflow.